Specifications of Basic I/O Units and High-density I/O Units
Terminal Connections
C200H-OC221 Contact Output Unit (8 Points)
Circuit Configuration
628
250 V AC 24 V DC max.
(inductive load: 2 A
resistive load: 2 A)
(16 A/Unit)
Note: There are no restrictions in the polarity
Max. Switching Capacity
Min. Switching Capacity
Relay
Service Life of Relay
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Weight
Output indicator
Internal
circuits
See note.
0
B0
L
c0
A0
1
B1
L
c1
A1
2
B2
L
c2
A2
3
B3
L
c3
A3
4
L
B4
c4
A4
5
B5
L
c5
A5
6
B6
L
c6
7
A6
B7
L
c7
A7
NC
B8
NC
A8
NC
B9
when connecting a DC power supply.
2 A 250 V AC (cosφ = 1), 2 A 250 V AC (cosφ = 0.4),
2 A 24 V DC (8 A/Unit)
10 mA 5 V DC
G6B-1174P-FD-US-M (24 V DC) with socket
Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
Service life will vary depending on the current and
ambient temperature.
10 ms max.
10 ms max.
1 (8 points/common)
10 mA 5 V DC max. 75 mA 26 V DC (8 points ON
simultaneously.)
250 g max.
OUT
L
OUT
L
COM
250 V AC 24 V DC max.