Omron SYSMAC CS Series Operation Manual page 388

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

PLC Setup
7-1-2-5
Special I/O Unit Cyclic Refreshing (CX-Programmer SIOU Refresh Tab
Page)
Item
Programming
Console address
Word
Cyclic Refresh-
+226
ing of Units 0 to
15
Cyclic Refresh-
+227
ing of Units 16
to 31
Cyclic Refresh-
+228
ing of Units 32
to 47
Cyclic Refresh-
+229
ing of Units 48
to 63
Cyclic Refresh-
+230
ing of Units 64
to 79
Cyclic Refresh-
+231
ing of Units 80
to 95
350
Settings
Bit(s)
0 to 15
0: Enabled
1: Disabled
Default: 0
0 to 15
0: Enabled
1: Disabled
Default: 0
0 to 15
0: Enabled
1: Disabled
Default: 0
0 to 15
0: Enabled
1: Disabled
Default: 0
0 to 15
0: Enabled
1: Disabled
Default: 0
0 to 15
0: Enabled
1: Disabled
Default: 0
Note If a Special I/O Unit is not refreshed periodically from the CPU Unit (at least
every 11 seconds), a CPU Unit monitoring error will occur. (The ERH indicator
and RUN indicator will be lit on the Special I/O Unit.) If cyclic I/O refreshing of
a Special I/O Unit is disabled, use the IORF(097) instruction to refresh the
Unit from the user program.
Function
These settings determine whether
data will be exchanged between the
specified Unit and the Special I/O
Unit's allocated words (10
words/Unit) during cyclic refreshing
for Special I/O Units.
Turn ON the corresponding bit to dis-
able cyclic refreshing when the Unit
will be refreshed in an interrupt task
by IORF(097), several Special I/O
Units are being used and you don't
want to extend the cycle time, or the
cycle time is so short that the Special
I/O Unit's internal processing can't
keep up.
(Special I/O Units can be refreshed
from the program with IORF(097).)
Section 7-1
Related
New
flags and
setting's
words
effective-
ness
---
Takes
effect at the
start of
operation