Omron SYSMAC CS Series Operation Manual page 644

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Specifications of Basic I/O Units and High-density I/O Units
2. Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CS1W-INT01 Interrupt Input Unit (16 Points)
Circuit Configuration
IN00
to
IN07
IN08
to
IN15
• Up to two Interrupt Input Units can be mounted to the CPU Rack.
• Interrupts cannot be used when an Interrupt Input Unit is mounted to an Expansion I/O Rack, i.e., it will be
treated as a 16-point Input Unit.
• Set the pulse width of signals input to the Interrupt Input Unit so they satisfy the above conditions.
606
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Current
ON Response Time
OFF Response Time
No. of Circuits
Number of Simultaneously ON
Points
Insulation Resistance
Dielectric Strength
Internal Current Consumption
Weight
470 Ω
3.3 kΩ
Input indicator
470 Ω
3.3 kΩ
24 V DC
20.4 to 26.4 V DC
3.3 kΩ
7 mA typical (at 24 V DC)
14.4 V DC min./3 mA min.
5 V DC max./1 mA max.
0.1 ms max.
0.5 ms max.
16 (8 points/common, 2 circuits)
100% simultaneously ON
20 MΩ between external terminals and the GR ter-
minal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
100 mA 5 V DC max.
270 g max.
0.5 ms min.
0.1 ms min.
Appendix A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1g/h-cpu_hCs1g/h-cpu_-ev1

Table of Contents