Omron SYSMAC CS Series Operation Manual page 744

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Specifications of Basic I/O Units and High-density I/O Units
Terminal Connections
12 V DC
+
Note 1. Refer to the Unit's operation manual for details on I/O bit allocation.
2. The Unit will have 128 dynamic output points when pin 1 of it's DIP switch is ON.
3. The user is not authorized to change the fuse.
C200H-MD215 24-V DC Input/Transistor Output Unit
Used for 16 Static Inputs and 16 Static Outputs
Output Specifications (Connector 1)
Input Specifications (Connector 2)
706
CN1
B
A
12
12
NC
NC
11
11
NC
NC
12 V DC
+V1
+V0
10
10
COM1
COM0
9
9
STB15
STB7
8
8
STB14
STB6
7
7
STB13
STB5
6
6
STB12
STB4
5
5
STB11
STB3
4
4
STB10
STB2
3
3
STB9
STB1
2
2
STB8
STB0
1
1
Max. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Fuses
Power for External Supply
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
High-speed Inputs
+
Keyboard, thumb-
wheel switch, etc.
Keyboard, thumb-
wheel switch, etc.
16 mA, 4.5 V DC to 100 mA, 26.4 V DC
800 mA/common, 1.6 A/Unit
0.1 mA max.
0.7 V max.
0.2 ms max.
0.6 ms max.
2 (8 points/common)
2 (1 fuse/common; fuses are not user-replaceable.)
45 mA 5 to 24 V DC±10% min.
(2.8 mA × number of ON outputs)
24 V DC
20.4 to 26.4 V DC
5.6 kΩ
4.1 mA (at 24 V DC)
14.4 V DC min.
5.0 V DC max.
2.5 ms/15 ms max. (switchable)
2.5 ms/15 ms max. (switchable)
2 (8 points/common)
8 points (connector 2 terminals 8 to 15, when set)
Pulse width: 1 ms/4 ms min. (switchable)
Appendix A
CN2
B
A
DATA0
DATA8
1
1
DATA1
DATA9
2
2
DATA2
DATA10
3
3
DATA3
DATA11
4
4
DATA4
DATA12
5
5
DATA5
DATA13
6
6
DATA6
DATA14
7
7
DATA7
DATA15
8
8
COM2
COM3
9
9
NC
10
10
NC
NC
11
11
NC
NC
12
NC
12