Specifications of Basic I/O Units and High-density I/O Units
CS1W-OD232 (32 Points, Sourcing)
Rated Voltage
Operating Load Voltage Range 20.4 to 26.4 V DC
Maximum Load Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Load Short-circuit Prevention
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption
External Power Supply
Weight
Accessories
Circuit Configuration
When the output current of any output exceeds the detection current, the output for that point will turn OFF. At
the same time, the ERR indicator will light and the corresponding flag (one for each common) in the Basic I/O
Unit Information Area (A050 to A089) will turn ON.
24 V DC
0.5 A/point, 2.5 A/common, 5.0 A/Unit (See note.)
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance. (Refer to the above Load
Short-circuit Protection.)
20 MΩ between the external terminals and the GR terminal
(100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1
minute at a leakage current of 10 mA max.
32 (16 points/common, 2 circuits)
5 V DC 270 mA max.
20.4 to 26.4 V DC, 70 mA min.
210 g max.
One connector for external wiring (soldered)
Note The maximum load currents will be 2.0 A/common and 4.0 A/Unit if a
pressure-welded connector is used.
Output Indicator
ERR indicator
Appendix A
667