Specifications of Basic I/O Units and High-density I/O Units
CS1W-OD291 Transistor Output Unit (96 Points, Sinking)
Circuit Configuration
Note 1. The ERR indicator will light if a fuse blows or if the external power supply is turned OFF, and the cor-
responding Flag in the Basic I/O Unit Information Area (A050 to A089) will turn ON.
2. The maximum load currents will be 1.0 A/common and 6.0 A/Unit if a pressure-welded connector is
used.
656
Rated Voltage
Operating Load Voltage
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
Accessories
Indicator
switch circuit
Output indicator
Blown fuse
detection
ERR indicator
circuit
12 to 24 V DC
10.2 to 26.4 V DC
0.1 A/point, 1.2 A/common, 7.2 A/Unit (See note 2.)
1.0 A/point, 10 ms max.
8.0 A/common, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
20 MΩ between the external terminals and the GR
terminal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
6 (16 points/common)
480 mA max. at 5 V DC
3 A (1 per common)
The fuse cannot be replaced by the user.
10.2 to 26.4 V DC, 100 mA min.
320 g max.
Two connectors for external wiring (soldered)
10.2 to
26.4 V DC
x 3 CN1 circuits
Fuse
10.2 to
26.4 V DC
x 3 CN2 circuits
Fuse
Appendix A