Conformance to EC Directives

6-4

Relay Output Noise Reduction Methods

Countermeasures
Countermeasure Examples
Circuit
CR method
Power
supply
and other conditions. You must therefore confirm that the overall machine
or equipment complies with EC Directives.
The CS-series PLCs conforms to the Common Emission Standards
(EN61000-6-4) of the EMC Directives. However, noise generated by relay out-
put switching may not satisfy these Standards. In such a case, a noise filter
must be connected to the load side or other appropriate countermeasures
must be provided external to the PLC.
Countermeasures taken to satisfy the standards vary depending on the
devices on the load side, wiring, configuration of machines, etc. Following are
examples of countermeasures for reducing the generated noise.
(Refer to EN61000-6-4 for more details.)
Countermeasures are not required if the frequency of load switching for the
whole system with the PLC included is less than 5 times per minute.
Countermeasures are required if the frequency of load switching for the whole
system with the PLC included is more than 5 times per minute.
When switching an inductive load, connect an surge protector, diodes, etc., in
parallel with the load or contact as shown below.
Current
Characteristic
AC
DC
Yes
Yes
If the load is a relay or solenoid, there is a
time lag between the moment the circuit is
opened and the moment the load is reset.
If the supply voltage is 24 or 48 V, insert
the surge protector in parallel with the
load. If the supply voltage is 100 to 200 V,
insert the surge protector between the
contacts.
Required element
The capacitance of the capacitor must
be 1 to 0.5 µF per contact current of
1 A and resistance of the resistor must
be 0.5 to 1 Ω per contact voltage of
1 V. These values, however, vary with
the load and the characteristics of the
relay. Decide these values from exper-
iments, and take into consideration
that the capacitance suppresses
spark discharge when the contacts
are separated and the resistance lim-
its the current that flows into the load
when the circuit is closed again.
The dielectric strength of the capacitor
must be 200 to 300 V. If the circuit is
an AC circuit, use a capacitor with no
polarity.