Omron SYSMAC CS Series Operation Manual page 304

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Analog Timer Units
Components and Switch Settings
Internal variable resistor
Sets variable resistance of specified
timer setting.
The settings of these resistors are
only effective when the selector
switch on the Unit is ON (set to the
right).
Numbers 0 to 3 correspond to timers
T0 to T3, respectively.
Set or adjust times using the flat-
blade screwdriver supplied with the
Unit. turning the variable resistor
clockwise to increase the time value.
Min.
Max.
INT/EXT selector switch
ON
Internal variable resistor
OFF
External variable resistor
T0
SW4
SW3
266
Timer pause input
TM001
SET
TIME UP
0 1 2 3
0
2
0
1
2
3
T1
T2
T3
SW2
SW1
Note
1. When the internal variable resistor is used, make sure that the external
variable resistor connector for the same timer number is open. Otherwise
the internal variable resistor settings will not function properly.
2. Use AWG 28 to AWG 22 lead wires for the external variable resistor con-
nectors.
3. Soldering is not required to wire the external variable resistor connectors.
Wire the connector as shown in the following diagram.
Analog Timer Unit
Timer set input
Resistance
value
Resistance
value
Resistance
value
Resistance
value
Timer status indicators
The SET indicators in the top row light when the corresponding
timer is operating and the TIME UP indicators in the bottom row
light when the corresponding time is up.
Time range setting
1
Each timer uses 2 pins. The upper 8 pins 8 to 1 are used for
3
timers T0 to T3 as follows:
(0: OFF, 1: ON)
Timer
Pin
8
T0
7
6
T1
5
NO
4
T2
3
NO
2
T3
1
External variable resistor connectors
Cable connector for when timer is set with external volume
instead of internal volume.
Turn OFF (set to left) the Internal/external volume selector
switch.
Numbers 0 to 3 correspond to timers T0 to T3.
The external volume resistance is 20 kΩ.
Use the following connectors. The C4K-CN223 (2 m) connector
with cable can also be used.
Name
Connector
IL-2S-S3L-(N)
Contact
IL-C2-1-10000
Timer up output
Setting value
Setting value
Setting value
Setting value
0.1 to 1 s
1 to 10 s
10 to 60 s 1 to 10 m
0
1
0
1
0
0
1
1
0
1
0
1
0
0
1
1
0
1
0
1
0
0
1
1
0
1
0
1
0
0
1
1
Model
Manufacturer
Japan Aviation
Electronics
Industry, Ltd.