Omron SYSMAC CS Series Operation Manual page 718

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Specifications of Basic I/O Units and High-density I/O Units
Terminal Connections
• When wiring, pay careful attention to the polarity. The load may operate if the polarity is reversed.
• Although the +V and COM terminals of rows A and B of CN1 and CN2 are internally connected, wire all
points completely.
Note The ON response time will be 120 µs maximum and OFF response time will be 300 µs maximum even if
the response times are set to 0 ms due to internal element delays.
680
Number of Simultaneously ON Points vs.
Ambient Temperature Characteristic
32 points at 34°C
I/O word "m+1"
I/O word "m"
24 V DC
32 points at 40°C
Input voltage: 24 V DC
Input voltage: 26.4 V DC
22 points at 55°C
16 points at 55°C
Ambient Temperature
I/O word "m+2"
24
V DC
24 V DC
Appendix A
I/O word "m+3"
24
V DC