Wiring
!Caution Be careful when connecting personal computers or other peripheral devices
External power supply
FG
AC Power Source
C200HW-PA204C Power Supply Unit
L2 /N 100 to
L1
L
NC
NC
to a PLC to which is mounted a non-insulated Unit (CS1W-CLK12/15(-V1),
CS1W-CLK13/53, or CS1W-ETN01) connected to an external power supply.
A short-circuit will be created if the 24 V side of the external power supply is
grounded and the 0 V side of the peripheral device is grounded. When con-
necting a peripheral device to this type of PLC, either ground the 0 V side of
the external power supply or do not ground the external power supply at all.
Non-insulated
DC power supply
24 V
0 V
0 V
Non-insulated Unit
Note
1. To prevent damage, be sure that the jumper bar on the voltage selector ter-
minals has been removed before applying 220 V AC power.
2. If a Power Supply Unit without a RUN output is being used, an output that
acts as a RUN output can be created by programming the Always ON Flag
(A1) as the execution condition for an output from an Output Unit.
• Supply 100 to 120 V AC or 200 to 240 V AC.
• The C200HW-PA204/PA204R/PA204C supplies 100 to 240 V AC (allow-
able voltage fluctuation range: 85 to 264 V AC). The C200HW-PA204/
PA204R/PA204C has a wide-range supply voltage (100 to 240 V AC), so
voltage selector terminals are not provided.
PA204C
3.5-mm self-rising screws
240 VAC
INPUT
ALARM
OUTPUT
30 VDC, 50 mA
NORMAL: ON
ALARM: OFF
24 V DC
power supply
Incorrect
Peripheral
cable
Shield
FG
GR
CPU Unit
Section 5-3
1:1 isolation
transformer
Alarm output (replacement notification
output)
ON: Power Supply Unit replacement
not required for at least 6 months.
OFF: Power Supply Unit replacement
required within 6 months.
SG
Peripheral device
FG
(e.g., personal
computer)
AC power
source
100 to 240 V AC
FG
311