Specifications of Basic I/O Units and High-density I/O Units
Circuit Configuration
Terminal Connections
• When wiring, pay careful attention to the polarity. The load may operate if the polarity is reversed.
• Although the +V and COM terminals of rows A and B are internally connected, wire all points completely.
C200H-OD218 Transistor Output Unit (32 Points)
648
Output indicator
I/O word "m + 1"
12 to 24 V DC
Max. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
I/O word "m"
12 to 24 V DC
16 mA 4.5 V DC to 100 mA 26.4 V DC (see below)
0.1 mA max.
0.8 V max.
0.1 ms max.
0.4 ms max.
1 (32 points/common)
180 mA 5 V DC max.
3.5 A (The fuse is not user-replaceable.)
110 mA 5 to 24 V DC±10% min.
(3.4 mA × number of ON pts)
180 g max.