B7A Interface Units
Wiring Methods
Standard Mode
High-speed Mode
252
Note
1. Confirm that terminals are connected correctly. If connections are incor-
rect, the internal components of the B7A Interface Unit and B7A Link Ter-
minal may be damaged.
2. Route the signal lines in separate ducts both inside and outside the control
panel to isolate them from power lines.
3. Connect cables at a distance that is within the range given in the specifi-
cations.
4. Always turn OFF the power to the CPU Unit and all other Units before con-
necting the communications cables.
5. Always lay communications cables within ducts.
Common Power Supply
B7A Interface Unit
SIG
SIG
12 to 24 VDC
Separate Power Supplies
B7A Interface Unit
SIG
SIG
12 to 24 VDC
Note If shielded cable is not used, the maximum transmission distance is 10 m
regardless of whether a common or separate power supplies are used. (Use
VCTF cable of 0.75 mm
Transmission distance: 100 m max.
Transmission cable: VCTF, 0.75 mm
min.
2
12 to 24 VDC
Transmission distance: 500 m max.
12 to 24 VDC
Transmission cable: VCTF, 0.75 mm
2
max.
2
or higher.)
Section 3-8
B7A Link Terminal
B7A Link Terminal
B7A Link Terminal
B7A Link Terminal