Omron SYSMAC CS Series Operation Manual page 124

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Specifications
Item
Error log
Serial communications Built-in peripheral port: Programming Device (including
Clock
Power OFF detection
time
Power OFF detection
delay time
Memory protection
Sending commands to
a Host Link computer
Remote programming
and monitoring
Communicating across
network layers
Storing comments in
CPU Unit
86
Specification
Up to 20 errors are stored in the error log. Information
includes the error code, error details, and the time the error
occurred.
A CS1-H CPU Unit can be set so that user-defined FAL
errors are not stored in the error log.
Programming Console) connections, Host Links, NT Links
Built-in RS-232C port: Programming Device (excluding
Programming Console) connections, Host Links, no-proto-
col communications, NT Links
Serial Communications Board (sold separately): Protocol
macros, Host Links, NT Links
Provided on all models. Accuracy: ± 30 s/mo. at 25°C
(accuracy varies with the temperature)
Note Used to store the time when power is turned ON and
when errors occur.
10 to 25 ms (not fixed)
0 to 10 ms (user-defined, default: 0 ms)
Held Areas: Holding bits, contents of Data Memory and
Extended Data Memory, and status of the counter Comple-
tion Flags and present values.
Note If the IOM Hold Bit in the Auxiliary Area is turned
ON, and the PLC Setup is set to maintain the IOM
Hold Bit status when power to the PLC is turned ON,
the contents of the CIO Area, the Work Area, part of
the Auxiliary Area, timer Completion Flag and PVs,
Index Registers, and the Data Registers will be
saved for up to 20 days.
FINS commands can be sent to a computer connected via
the Host Link System by executing Network Communica-
tions Instructions from the PLC.
Host Link communications can be used for remote pro-
gramming and remote monitoring through a Controller Link
System or Ethernet network.
Remote programming and monitoring using the Support
Software, as well as FINS message communications, can
be conducted across network layers, including other types
of network.
Pre-Ver. 2.0:
Three layers
Version 2.0 or later:
Eight layers for Controller Link and
Ethernet (see note). Three layers for
DeviceNet and SYSMAC LINK.
Note To construct a network of eight layers, it is necessary
to use the CX-Integrator or CX-Programmer (version
4.0 or higher) to set routing tables.
I/O comments can be stored as symbol table files in the
Memory Card, EM file memory, or comment memory (see
note).
Note Comment memory is supported for CS/CJ-series
CPU Units with unit version 3.0 or later only.
Section 2-1
Reference
Error log: Programming Manual
(W394)
Serial communications systems:
2-5-1 Serial Communications
System
Serial communications: Program-
ming Manual (W394)
Clock: Programming Manual
(W394)
Power OFF operation and power
OFF detection time: 10-3 Power
OFF Operation
Power OFF detection delay time:
Programming Manual (W394)
Memory protection: 9-2-3 Data
Area Properties
Host Links and non-solicited
communications: 2-5-2 Systems
Remote programming and moni-
toring: Programming Manual
(W394)
Controller Link 2-5-3 Communi-
cations Network System
Host Links and FINS message
service: 2-5-2 Systems
I/O comments: CX-Programmer
Operation Manual (W446)
Storing comments in CPU Unit:
Programming Manual (W394)