Omron SYSMAC CS Series Operation Manual page 309

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Introduction
8. PLC Setup Settings
With the PLC in PROGRAM mode, change the settings in the PLC Setup
as necessary from the Programming Device (CX-Programmer or Program-
ming Console). (Another method is to change the PLC Setup in CX-Pro-
grammer and transfer it to the CPU Unit.)
See 7-1 PLC Setup for details.
9. DM Area Settings
a) Use a Programming Device (CX-Programmer or Programming Con-
sole) to make any necessary settings in the parts of the DM Area that
are allocated to Special I/O Units, CS-series CPU Bus Units, and Inner
Boards.
b) Reset the power (ON → OFF → ON) or toggle the Restart Bit for each
Unit or Board. See the Unit's or Board's Operation Manual for details.
10. Writing the Program
Write the program with a Programming Device (CX-Programmer or Pro-
gramming Console.)
11. Transferring the Program (CX-Programmer Only)
With the PLC in PROGRAM mode, transfer the program from CX-Pro-
grammer to the CPU Unit. See 7-1 Program Transfer in the CS/CJ Series
Programmable Controllers Programming Manual (W394) for details.
12. Testing Operation
a) Checking I/O Wiring
Output wiring With the PLC in PROGRAM mode, force-set output bits
Input wiring
b) Auxiliary Area Settings (As Required)
Check operation of special Auxiliary Area Settings such as the follow-
ing:
Output OFF
Bit
Hot Start Set-
tings
c) Trial Operation
Test PLC operation by switching the PLC to MONITOR mode.
d) Monitoring and Debugging
Monitor operation from the Programming Device. Use functions such
as force-setting/force-resetting bits, tracing, and online editing to de-
bug the program.
See SECTION 7 Program Transfer, Trial Operation, and Debugging in
the CS/CJ Series Programmable Controllers Programming Manual
(W394) for details.
13. Saving and Printing the Program
14. Running the Program
Switch the PLC to RUN mode to run the program.
and check the status of the corresponding outputs.
Activate sensors and switches and either check the status
of the indicators on the Input Unit or check the status of the
corresponding input bits with the Programming Device's
Bit/Word Monitor operation.
When necessary, turn ON the Output OFF Bit (A50015)
from the program and test operation with the outputs
forced OFF.
When you want to start operation (switch to RUN mode)
without changing the contents of I/O memory, turn ON the
IOM Hold Bit (A50012).