Specifications of Basic I/O Units and High-density I/O Units
3. Connect power supply wiring to every COM terminal, even though the COM terminals are connected
internally.
CS1W-OD261 Transistor Output Unit (64 Points, Sinking)
Circuit Configuration
Rated Voltage
Operating Load Voltage Range 10.2 to 26.4 V DC
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
Accessories
Output indicator
12 to 24 V DC
0.3 A/point, 1.6 A/common, 6.4 A/Unit
3.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
20 MΩ between the external terminals and the GR
terminal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
64 (16 points/common, 4 circuits)
5 V DC 390 mA max.
None
10.2 to 26.4 V DC, 50 mA min.
260 g max.
Two connectors for external wiring (soldered)