Error Processing
11-2-11 Battery Error Check
Battery error occurred.
Battery-free operation
required?
11-2-12 Environmental Conditions Check
Yes
No
Environmental conditions check
Is the ambient
temperature
below 55°C?
Is the ambient
temperature above
0°C?
Is the ambient humidity
between 10% and
90%?
Is noise being
controlled?
Is the installation
environment okay?
End.
Note Check for corrosive gases, flammable gases, dust, dirt, salts, metal dust,
direct light, water, oils, and chemicals.
Set the PLC Setup so that battery
errors are not detected. (DM Area
contents may be unstable when this
setting is used.)
Refer to the CS/CJ Programming
Manual for details.
The Battery is missing or the voltage
has dropped. Replace the Battery.
No
Consider using a
fan or cooler.
Yes
No
Consider using a
heater.
Yes
No
Consider using an
an air conditioner.
Yes
Install surge pro-
tectors or other
No
noise-reducing
equipment at
noise sources.
Yes
Check the struc-
No
ture of the panel
and the installa-
tion site.
(See note.)
Yes
Section 11-2
571