Specifications of Basic I/O Units and High-density I/O Units
CS1W-OD262 (64 Points, Sourcing)
Circuit Configuration
When overcurrent is detected, the ERR indicator will light. At the same time, the corresponding flag (one for
each common) in the Basic I/O Unit Information Area (A050 to A089) will turn ON.
670
Rated Voltage
Operating Load Voltage Range 20.4 to 26.4 V DC
Maximum Load Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Load Short-circuit Prevention
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption
External Power Supply
Weight
Accessories
Output indicator
ERR indicator
24 V DC
0.3 A/point, 1.6 A/common, 6.4 A/Unit
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance. (Refer to the
above Load Short-circuit Protection.)
20 MΩ between the external terminals and the GR
terminal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
64 (16 points/common, 4 circuits)
5 V DC 390 mA max.
20.4 to 26.4 V DC, 130 mA min.
270 g max.
Two connectors for external wiring (soldered)
Appendix A