Specifications of Basic I/O Units and High-density I/O Units
C200H-ID212 DC Input Unit (16 Points)
Circuit Configuration
Terminal Connections
604
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Weight
IN
3 kΩ
IN
0.01
µF
COM
24 V DC
24 V DC
24 V DC
20.4 to 26.4 V DC
3 kΩ
7 mA typical (at 24 V DC)
14.4 V DC min.
5.0 V DC max.
1.5 ms max. (at 24 V DC, 25°C)
1.5 ms max. (at 24 V DC, 25°C)
1 (16 points/common)
10 mA 5 V DC max.
300 g max.
1.8
kΩ
Input indicator
0
B0
1
A0
2
B1
3
A1
4
B2
5
A2
6
B3
7
A3
8
B4
9
A4
10
B5
11
A5
12
B6
13
A6
14
B7
15
A7
B8
NC
COM
A8
B9
NC