Omron SYSMAC CS Series Operation Manual page 654

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Specifications of Basic I/O Units and High-density I/O Units
Terminal Connections
I/O word "m+1"
24
V DC
• The input power polarity can be connected in either direction provided that the same polarity be set for
rows A and B.
• COM0, COM1, COM2, and COM3 have two pins each. Although they are internally connected, wire all
points completely.
Note The ON response time will be 120 µs maximum and OFF response time will be 300 µs maximum even if
the response times are set to 0 ms due to internal element delays.
616
Number of Simultaneously ON Points vs.
Ambient Temperature Characteristic
64 points
64 points
64 points
at 25°C
at 36°C
at 52°C
Input voltage: 24 V DC
Input voltage: 26.4 V DC
Ambient Temperature
I/O word "m"
I/O word "m+2"
24
V DC
24
V DC
Input voltage: 20.4 V DC
48 points at 55°C
32 points at 55°C
28 points at 55°C
I/O word "m+3"
24
V DC
Appendix A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1g/h-cpu_hCs1g/h-cpu_-ev1

Table of Contents