Omron SYSMAC CS Series Operation Manual page 353

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Wiring
RUN Output
(C200HW-PA204R/209R)
Wiring
!Caution Tighten the AC power supply terminal block screws to the torque of 0.8 N·m.
3. Do not apply a voltage or connect a load to the alarm output that exceeds
the rated voltage or load.
This output is ON whenever the CPU Unit is operating in RUN or MONITOR
mode; it is OFF when the CPU Unit is in PROGRAM mode or a fatal error has
occurred.
The RUN output can be used to control external systems, such as in an emer-
gency stop circuit that turns off the power supply to external systems when
the PLC is not operating. (See 5-1 Fail-safe Circuits for more details on the
emergency stop circuit.)
Contact
SPST-NO
form
Maximum
250 V AC: 2 A for resistive loads
switching
capacity
24 V DC: 2 A
Terminal screws
Recommended wire size
Recommended tightening
torque
Recommended crimp terminals
7 mm max.
Manufacturer
JST Mfg.
Note
1. Use crimp terminals for wiring.
2. Do not connect bare stranded wires directly to the terminals.
M3.5 self-raising terminals
Loose screws may result in short-circuit, malfunction, or fire.
Note
1. Supply power to all of the Power Supply Units from the same source.
C200HW-PA204R
0.5 A for inductive loads
M3.5 self-rising screws
AWG 20 to 14 (0.517 to 2.08 mm
0.8 N·m
7 mm max.
Models
V1.25-YS3A
Y-shaped termi-
nal with sleeve
V1.25-M3(RAV1.25-3.5) Round terminal
with sleeve
V2-YS3A
Y-shaped termi-
nal with sleeve
V2-M3(RAV2-3.5)
Round terminal
with sleeve
20 mm max.
Torque to 0.8 N·m
Section 5-3
C200HW-PA209R
SPST-NO
240 V AC:2 A for resistive loads
120 V AC:0.5 A for inductive loads
24 V DC: 2 A for resistive loads
2 A for inductive loads
2
)
Shape
Applicable wire range
(stranded wire)
0.25 to 1.65 mm
22 to 16)
1.04 to 2.63 mm
16 to 14)
2
(AWG
2
(AWG
315