Auxiliary Area
Name
Explicit Communications Error
Flag
Network Communications
Error Flag
Network Communications
Response Code
Name
SYSMAC BUS Master 1
Restart Bit
SYSMAC BUS Master 0
Restart Bit
Information on Explicit Message Instructions
Address
A21300 to
Turn ON when an error occurs in executing an Explicit Mes-
A21307
sage Instruction (EXPLT(720), EGATR(721), ESATR(722),
ECHRD(723), or ECHWR(724)).
Bits 00 to 07 correspond to communications ports 0 to 7.
The corresponding bit will turn ON both when the explicit
message cannot be sent and when an error response is
returned for the explicit message.
The status will be maintained until the next explicit message
communication is executed. The bit will always turn OFF
when the next Explicit Message Instruction is executed.
A21900 to
Turn ON if the explicit message cannot be sent when execut-
A21907
ing an Explicit Message Instruction (EXPLT(720),
EGATR(721), ESATR(722), ECHRD(723), or ECHWR(724)).
Bits 00 to 07 correspond to communications ports 0 to 7.
The corresponding bit will turn ON when the explicit mes-
sage cannot be sent.
The status will be maintained until the next explicit message
communication is executed. The bit will always turn OFF
when the next Explicit Message Instruction is executed.
A203 to
The following codes will be stored when an Explicit Message
A210
Instruction (EXPLT(720), EGATR(721), ESATR(722),
ECHRD(723), or ECHWR(724)) has been executed.
A203 to A210 correspond to communications ports 0 to 7.
If the Explicit Communications Error Flag turns OFF, 0000
hex is stored.
If the Explicit Communications Error Flag is ON and the Net-
work Communications Error Flag is ON, the FINS end code
is stored.
If the Explicit Communications Error Flag is ON and the Net-
work Communications Error Flag is OFF, the explicit mes-
sage end code is stored.
During communications, 0000 hex will be stored and the
suitable code will be stored when execution has been com-
pleted. The code will be cleared when operation is started.
SYSMAC BUS Communications Information
Address
A52614
Turn this bit ON to restart SYSMAC BUS Remote I/O Master
Unit 1. (Turned OFF automatically when restart processing
is completed.)
A52615
Turn this bit ON to restart SYSMAC BUS Remote I/O Master
Unit 0. (Turned OFF automatically when restart processing
is completed.)
Description
Description
Section 9-16
Access
Read-only
Read-only
Read-only
Access
Read/write
Read/write
455