Relay Outputs; Nos. 4204 And 4229 Output Reiay Modules; 4204Setup - ADEMCO via30 Installation Instructions Manual

Hide thumbs Also See for via30:
Table of Contents

Advertisement

RELAY OUTPUTS
Nos. 4204 and 4229
Output Relay Modules
4204 Setup
4229 Setup
The Ademco
v/a30 can support relay outputs via the use of either a 4204 (4
outputs) or a 4229 (2 outputs). These modules provide form C (normally open
and normally closed) dry contacts on relays that can be programmed to activate or
-
deactivate to perform some action in response to a predetermined event such as
-
turning on lights and/or closing a fire door in the event of a fire alarm condition.
There are many different uses for these relays, some of which are suggested in
the table on page 44.
The unit can be located inside the control's cabinet or remotely (see MOU/VT//VG
THE CONTROL, LOCK, & PC BOARD section and the instructions that accom-
pany the unit).
The 4204 Relay Unit has 4 Form C relays. Each relay can be used independently
for different functions. The following steps should be taken to properly set up the
4204:
1.
2.
3.
4.
Connect
the 4204 to the control's
remote
console
terminals
(4-7), using standard 4-conductor twisted cable (for long wiring runs) or the
connector supplied with the 4204 (as shown in the Summary of Connections
diagram).
Set the 4204's DIP switch
for a device address of "1"
(switch
2
"OFF" and switches 3, 4, 5 "ON"). Switch 1 determines
the unit's cover tam-
per response ("ON'" = disabied, "OFF" = enabled).
Note:
Some "early" units have only a 4-position DIP switch. Set 1 to "OFF"
and 2, 3, 4 to "ON".
During programming
(summarized here, but see the detaiied procedure
in the PROGRAMMING THE SECURITY CONTROL section):
a.
Program a"~ in field 25.
b.
Program fields '80 (Output Relays) and 81 (Zone Lists) for the desired
relay responses.
Connect the desired fieid wiring to the unit's reiay contact terminals.
The 4229 Wired Expansion/Relay Unit has 8 hard-wired zones and 2 Form C re-
lays. Each relay can be used independently for different functions. The foilowing
steps should be taken to properly setup the 4229:
1. Connect
the 4229 to the controi's
remote
consoie
terminais
(4-7),
using standard 4-conductor
twisted cabie (for long wiring runs) or the
connector suppiied with the 4229 (as
shown in the Summary of Connections
diagram).
2. Set the 4229's DiP switch for a device address of *'1'" (switch 2
"OFF" and switches 3, 4, 5 "ON"). Switch 1 determines zone A's response
time ("ON" = normal response, "OFF"= fast response).
3.
During programming (summarized here, but see the detailed procedure
in the PROGRAMMING THE SECUR/TY CONTROL section):
a.
Program a"2 in field *25.
b.
Program fieids 8O (Output Relays) and 81 (Zone Lists) for the desired
reiay responses.
c.
In field
56 (zone programming), assign zone numbers 10-17 to the
4229's wired expansion zones.
4.
Connect the desired fieid wiring to the unit's reiay contact terminais.
–12–

Advertisement

Table of Contents
loading

Table of Contents