8-3 Vibration Suppression Parameters
Pn200
Adaptive Filter Selection
Setting
0 to 4
range
Explanation of Set Values
Set value
0
Disabled. The current values are held for the parameters related to notch filters 3 and 4.
One adaptive filter is enabled. The parameter related to notch filter 3 is updated based on the
1
applicable result.
Two adaptive filter is enabled. The parameters related to notch filters 3 and 4 are updated
2
based on the applicable result.
The resonance frequency is measured. The measurement result can be checked using CX-
3
Drive. The current values are held for the parameters related to notch filters 3 and 4.
Adaptive result is cleared.Parameters related to notch filters 3 and 4 are disabled and the
4
adaptive result is cleared.
Set the operation of the adaptive filter.
The adaptive filter is normally disabled in the Torque Control Mode.
Pn201
Notch 1 Frequency Setting
Setting
50 to 5,000
range
Set the frequency of resonance suppression notch filter 1.
The notch filter function will be disabled if this parameter is set to 5,000.
Pn202
Notch 1 Width Setting
Setting
0 to 20
range
Set the width of resonance suppression notch filter 1 to one of 20 levels.
Increasing the set value widens the notch width. Normally, use the default set value.
Pn203
Notch 1 Depth Setting
Setting
0 to 99
range
Set the notch depth of resonance suppression notch filter 1.
Increasing the set value shortens the notch depth and the phase lag.
Pn204
Notch 2 Frequency Setting
Setting
50 to 5,000
range
Set the notch frequency of resonance suppression notch filter 2.
The notch filter function will be disabled if this parameter is set to 5,000.
Pn205
Notch 2 Width Setting
Setting
0 to 20
range
Select the notch width of resonance suppression notch filter 2.
Increasing the set value widens the notch width. Normally, use the default set value.
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8-3 Vibration Suppression Parameters
−
Unit
Description
Unit
Hz
−
Unit
−
Unit
Unit
Hz
−
Unit
Position Speed Fully-closed
Default
Power OFF
0
setting
and ON
Default
Power OFF
5000
setting
and ON
Default
Power OFF
2
setting
and ON
Default
Power OFF
0
setting
and ON
Default
Power OFF
5000
setting
and ON
Default
Power OFF
2
setting
and ON
−
All
−
8
All
−
All
−
All
−
All
−
8-20