8-1 Basic Parameters
Pn003
Realtime Autotuning Machine Rigidity Setting
Setting
0 to 31
range
 Default settings:
* Pn003 = 11 - For 200V drives of 1 kW or upper and 400V drives
 Set the machine rigidity to one of 32 levels when realtime autotuning is enabled.
 If the set value is changed suddenly by a large amount, the gain may change rapidly, subjecting
the machine to shock. Always start with a small setting, and gradually increase the setting while
monitoring machine operation.
Pn004
Inertia Ratio
Setting
0 to 10,000
range
 Set the load inertia as a percentage of the motor rotor inertia.
 Pn004 = (Load inertia / Rotor inertia) × 100%
 When realtime autotuning is enabled, the inertia ratio is continuously estimated and saved in
EEPROM every 30 minutes.
 If the inertia ratio is set correctly, the setting unit for the Speed Loop Gain (Pn101) and Speed Loop
Gain 2 (Pn106) is Hz.
If the Inertia Ratio (Pn004) is set larger than the actual value, the setting for speed loop gain will
8
increase. If the Inertia Ratio (Pn004) is set smaller than the actual value, the setting for speed loop
gain will decrease.
Pn005
Command Pulse Input Selection
Setting
0 or 1
range
Explanation of Set Values
value
0
1
 Selects whether to use photocoupler or input for line driver only for the command pulse input.
 When using a Servo Relay Unit cable, set to 0 (photocoupler input).
Pn006
Command Pulse Rotation Direction Switching Selection
Setting
0 or 1
range
8-3
Unit
Low
Low
Pn003
0.1 - - - - - - - - - - - - - - - 31
Low
Unit
Unit
Set
Photocoupler input (+PULS: CN1 pin 3, -PULS: CN1 pin 4, +SIGN: CN1 pin 5, -SIGN: CN1
pin 6)
Input for line driver only (+CWLD: CN1 pin 44, -CWLD: CN1 pin 45, +CCWLD: CN1 pin 46,
-CCWLD: CN1 pin 47)
Unit
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Default
setting
←Machine rigidity→
High
←Servo gain→
High
←Responsiveness→
High
Default
%
setting
Default
setting
Description
Default
setting
All
Power OFF
13 *
and ON
All
Power OFF
250
and ON
Position Fully-closed
Power OFF
0
Yes
and ON
Position Fully-closed
Power OFF
0
Yes
and ON