3-1 Servo Drive Specifications
R88D-KT30H/R88D-KT50H
Main Circuit Terminal Block Specifications
Symbol
L1
L2
L3
L1C
L2C
B1
B3
3
B2
NC
U
V
W
 Tighten the terminal block screws to the torque of 0.75 N•m (M4) or 1.5 N•m (M5).
 If the torque for terminal block screws exceeds 1.2 N•m (M4) or 2.0 N•m (M5), the terminal block
may be damaged.
 Tighten the fixing screw of the terminal block cover to the torque of 0.2 N•m (M3).
 Tighten the ground screws to the torque of 0.7 to 0.8 N•m (M4) or 1.4 to 1.6 N•m (M5).
 Never connect an External Regeneration Resistor between the B1 and NC terminals.
3-11
Name
Main circuit power
supply input
Control circuit power
supply input
External Regeneration
Resistor connection
terminals
Do not connect.
Motor connection
terminals
Precautions for Correct Use
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Function
R88D-KT@H (3 to 5 kW):
3-phase 200 to 230 VAC (170 to 253 V) 50/60 Hz
R88D-KT@H : Single-phase 200 to 230 VAC (170 to 253 V) 50/60
Hz
Normally B2 and B3 are connected. Do not short B1 and B2. Doing
so may cause malfunctions. If there is high regenerative energy,
remove the short-circuit bar between B2 and B3 and connect an
External Regeneration Resistor between B1 and B2.
Phase U
These are the output terminals to the Servomotor.
Be sure to wire them correctly.
Phase V
Phase W

Hide quick links: