12-2 Parameter List
016
017
Note 1: The default setting is 11 for 200-V Servo Drives of 1 kW or higher and 400-V Servo Drives.
Note 2: The default setting is 0 for 100-V Servo Drives of 400 W, 200-V Servo Drives of 750 W to
12
12-13
Parameter
name
Select the Regeneration Resistor used.
Use the Built-in Resistor.
Triggering of regeneration overload
0
protection (Alarm No. 18) depends on
the Built-in Resistor (with approx. 1%
duty).
Use an External Resistor.
The regeneration processing circuit
Regeneration
operates and regeneration overload
Resistor
1
protection (Alarm No. 18) is triggered
Selection
when the operating rate of the
Regeneration Resistor exceeds 10%.
Use an External Resistor.
2
Regeneration overload protection
(Alarm No. 18) does not operate.
No Regeneration Resistor
3
All regeneration power is processed
with built-in capacitors.
Select the type of load ratio calculation for
the External Regeneration Resistor.
Regeneration load ratio is 100% when
0
operating rate of the External
External
Regeneration Resistor is 10%.
Regeneration
1
Reserved
Resistor Setting
2
Reserved
3
Reserved
4
Reserved
5 kW, and 400-V Servo Drives of 5 kW or lower.
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Default
Description
setting
See
Note 2
0
Power
Setting
supply
Unit
range
OFF to
ON
0 to 3
Yes
0 to 4
Yes