4-3 Wiring Conforming to EMC Directives
Noise Filter for Power Supply Input
We recommend you to use the noise filter for the Servo Drive.
Single-phase R88D-K@A5L@@
Single-phase R88D-K@04L@@
Single-phase
Single-phase
4
Single-phase
Single or 3-
 For operations, if no-fuse breakers are installed at the top and the power supply line is wired from
the lower duct, use metal tubes for wiring or make sure that there is adequate distance between
the input lines and the internal wiring. If input and output lines are wired together, noise resistance
will decrease.
 The noise filter must be installed as close as possible to the entrance of the control panel. Wire
as shown at the left in the following illustration.
4-37
Drive
Phase
Model
R88D-K@01L@@
R88D-K@02L@@
R88D-K@01H@@
3-phase
R88D-K@02H@@
3-phase
R88D-K@04H@@
3-phase
R88D-K@08H@@
R88D-K@10H@@
phase
R88D-K@15H@@
R88D-K@20H@@
R88D-K@30H@@
R88D-K@50H@@
R88D-K@75H@@
R88D-K@150H@@
R88D-K@06F@@
3-phase
R88D-K@10F@@
R88D-K@15F@@
R88D-K@20F@@
R88D-K@30F@@
R88D-K@50F@@
R88D-K@75F@@
R88D-K@150F@@
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Noise filter for power supply input
Rated
Model
current
SUP-EK5-ER-6
5A
3SUP-HU10-ER-6
10A
SUP-EK5-ER-6
5A
3SUP-HU10-ER-6
10A
SUP-EK5-ER-6
5A
3SUP-HU10-ER-6
10A
SUP-EK5-ER-6
5A
3SUP-HU10-ER-6
10A
3SUP-HU30-ER-6
30A
3SUP-HU50-ER-6
50A
3SUP-HL50-ER-6B
50A
FS5559-60-34
60A
FS5559-80-34
80A
FN258L-16-07
16A
FN258L-30-07
30A
FN258-42-07
42A
Leakage current
Manufacturer
(60 Hz) max
1.0mA (at 250 VAC)
3.5mA (at 500 VAC)
1.0mA (at 250 VAC)
3.5mA (at 500 VAC)
1.0mA (at 250 VAC)
Okaya
3.5mA (at 500 VAC)
Electric
1.0mA (at 250 VAC)
Industries
Co., Ltd.
3.5mA (at 500 VAC)
3.5mA
(at 500 VAC)
3.5mA
(at 500 VAC)
8.0mA
(at 500 VAC)
1.35mA
(at 480 VAC/50 Hz)
1.35mA
(at 480 VAC/50 Hz)
0.8mA
Schaffner
(at 440 VAC/50 Hz)
EMC Inc.
0.8mA
(at 440 VAC/50 Hz)
25.8mA
(at 440 VAC/50 Hz)