Forming the DC link capacitors

Description
The DC link capacitors must be reformed if Basic Line Modules, Active Line Modules and
Motor Modules have not been used for more than two years. If this is not carried out, the
units could be damaged after the DC-link voltage is applied under load.
If the cabinet is commissioned within two years of its date of manufacture, the DC-link
capacitors do not need to be re-formed. The date of manufacture can be taken from the
serial number on the rating plate.
Note
Storage period
It is important that the storage period is calculated from the date of manufacture and not from
the date that the equipment was shipped.
Rating plate
Figure 7-28
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Rating plate using an Active Line Module as example
Maintenance and servicing
7.6 Forming the DC link capacitors