1.3
Electrical Specifications and Environmental Conditions
Electromagnetic compatibility (EMC) refers to the ability of electrical equipment to function
properly in its electromagnetic environment without interfering with the environment. Table 1-2
and Table 1-3 describe the electrical specification environmental condition standards that the
C06/C07 should comply with. Programmable logic controller standard: IEC61131-2, GB15969.
Table 1-2 Electrical Specifications
Electromagnetic Compatibility - Immunity
Electrostatic
IEC61000-4-2
Electrical Fast Transient Burst
IEC61000-4-4
Surge IEC61000-4-5
Radio
Electromagnetic
Radiation
IEC61000-4-3
RF Field Induced Conducted
Disturbance
IEC61000-4-6
DC power input port for short
interruptions
changes
IEC61000-4-29
Environmental Testing
High
temperature
IEC60068-2
Low
temperature
IEC60068-2
High
IEC60068-2
Low
IEC60068-2
High and low temperature cycle
operation IEC60068-2
High
temperature
IEC60068-2
Low
temperature
IEC60068-2
Thermal shock IEC60068-2
High temperature and high
humidity IEC60068-2
Alternating
IEC60068-2
Discharge
Frequency
Field
and
voltage
operation
operation
temperature
startup
temperature
start
storage
storage
Damp
Heat
Contact discharge: ±4KV
Air discharge: ±8KV
Power cord: 2KV, 5KHz
Signal line: 2KV, 5KHz (I/O coupling clip)
1KV, 5KHz (communication coupling clip)
Power cord: 2KV (asymmetric), 1KV (symmetric)
80MHz~1GHz,10V/m,80%AM(1KHz)
0.15MHz~80MHz,10V/m,80%AM(1KHz)
Short interruption: 10ms
Voltage change: 80%~120%, 100ms
60℃ for 16 hours
-10℃ 16 hours
60℃ for 2 hours
-10℃ for 2 hours
-10°C ~60°C dwell time 3 hours, temperature rise rate
1°C/min, 2 cycles
70℃ for 72 hours
-40℃ 72 hours
-40℃~70℃ dwell time 3 hours, temperature change time
<1min, 5 cycles
40℃ for 48 hours
25℃~55℃ 95% 2 cycles
9
Need help?
Do you have a question about the MAT-LC-C Series and is the answer not in the manual?