5. Obtain current speed by average value
0unction:HSC_GETSPEED-AVG
Parameter
I/O
MOD_ID
IN
CH_ID
IN
BUFSIZE
IN
DeadBand
IN
SPEED
OUT
STA
OUT
7. Obtain current count status
Function:HSC_GETSTA
Paramete
I/O
r
MOD_ID
IN
Description
Type
Module
DWORD
address
Channel
BYTE
address
Average
DI1, NT
value buffer
Dead zone
DWORD
value
Count
DWORD
speed
Module
BYTE
status byte
Descripti
Type
on
Module
DWORD
address
152
Initiali
zation
PLC 16# 0a000605, Module Id of
0
hardware configuration
PLC local value (0-5) HSC
0
module value (0, 1)
Average buffer size is greater
16
than 0 and less than 64
If the difference between the
average value and the existing
value is less than the dead zone
20000
value, the average value shall
prevail, and the value greater than
the dead zone average value is
the existing value
0
Hz
Module status byte 0: OK 2:
invalid parameter 5: Incorrect
0
module parameter 7: Module
does not respond 8: Module link
layer error.
Initiali
zation
PLC 16# 0a000605, Module Id of
0
hardware configuration
Remark
Remark
Need help?