Corrective maintenance
12.1 Service and maintenance for the converter
Requirement
You have an SD card with the appropriate firmware, or you have an empty SD card with a
maximum capacity of 32 GB onto which you can load the firmware.
You can download the available firmware versions at the following link
support.industry.siemens.com/cs/ww/en/ps/29596/dl).
Procedure
Proceed as follows to update the firmware using an SD card:
1. Switch off the converter.
2. Insert the SD card into the converter and switch on the converter.
The new firmware is installed. This process takes approximately two minutes.
3. Switch the converter off and remove the SD card.
4. Switch on the converter again. Check whether the new version is installed. The firmware
version of the converter is displayed on the home page of the web server.
More information
You can find more information about the SD card in Section "AUTOHOTSPOT".
12.1.3

Replacing the converter

Overview
You may only replace a converter with another converter if certain requirements are adhered to.
484
RDY
COM
Explanation of LED displays
Firmware update is active:
Do not switch off the power supply.
Do not disconnect the motor from the converter.
-
Firmware update is completed
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA