System messages
11.3 Faults and alarms
Remedy:
- Check the heat sink fan and replace if necessary.
- For communication errors, update the software or replace the power unit.
Note:
- If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched off the fan, and therefore can no longer evaluate the feedback signal.
F30059
Power unit: Internal fan 1 defective
Message class:
Auxiliary unit faulted (20)
Message value:
%1
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
The feedback signal of internal fan 1 signals a fault, or there is a communication error with the fan.
Fault value (r0949, interpret decimal):
0: Feedback signal of the fan signals a fault
1: Internal communication error to the fan
Remedy:
- Check internal fan 1 and replace if necessary.
- For communication errors, update the software or replace the power unit.
Note:
If the fault can be acknowledged, this does not necessarily mean that the cause of the fault has been resolved. It is also
possible that the software switched off the fan, and therefore can no longer evaluate the feedback signal.
F30062
Bypass contactor opened under current
Message class:
Infeed faulted (13)
Message value:
-
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
The bypass contactor of the precharging unit has been opened under current.
Possible causes:
- A defect at the bypass contactor
Remedy:
It is urgently recommended that the components involved are replaced to prevent serious damage to the entire converter
line-up.
F30068
Power unit: undertemperature inverter heat sink
Message class:
Power electronics faulted (5)
Message value:
%1
Component:
Power Unit
Response:
OFF2
Acknowledgment: IMMEDIATELY
Cause:
The actual inverter heat sink temperature is below the permissible minimum value.
Possible causes:
- The power unit is being operated at an ambient temperature that lies below the permissible range.
- The temperature sensor evaluation is defective.
Fault value (r0949, interpret decimal):
Inverter heat sink temperature [0.1 °C].
Remedy:
- Ensure that higher ambient temperatures prevail.
- Replace the power unit.
450
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA