System messages
11.3 Faults and alarms
A01007
POWER ON for DRIVE-CLiQ component required
Message class:
General drive fault (19)
Message value:
Component number: %1
Component:
None
Response:
NONE
Acknowledgment: NONE
Explanation of the
For %1
message value:
 
Component in target topology
Cause:
A DRIVE-CLiQ component must be switched on again (POWER ON) (e.g. due to a firmware update).
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Note:
For a component number = 1, a POWER ON of the Control Unit is required.
Remedy:
- Switch off the power supply of the specified DRIVE-CLiQ component and switch it on again.
- For SINUMERIK, auto commissioning is prevented. In this case, a POWER ON is required for all components and the auto
commissioning must be restarted.
A01009
Control Unit overtemperature
Message class:
Overtemperature of the electronic components (6)
Message value:
-
Component:
Control Unit (CU)
Response:
NONE
Acknowledgment: NONE
Cause:
The temperature (r0037[0]) of the converter has exceeded the specified limit value.
Remedy:
- Check the converter air intake.
- Check the converter fan.
Note:
The alarm is automatically withdrawn once the limit value has been fallen below.
F01011
Download interrupted
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Message value:
%1
Component:
None
Response:
NONE
Acknowledgment: IMMEDIATELY
Cause:
The project download was interrupted.
Fault value (r0949, interpret decimal):
1: The user prematurely interrupted the project download.
2: The communication cable was interrupted (e.g. cable breakage, cable withdrawn).
3: The project download was prematurely exited by the commissioning tool.
100: Different versions between the firmware version and project files which were loaded by loading into the file system
"Download from memory card".
Note:
The response to an interrupted download is the state "first commissioning".
Remedy:
- Check the communication cable.
- Download the project again.
- Boot from previously saved files (switch-off/switch-on or p0976).
- When loading into the file system (download from memory card), use the matching version.
330
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA