Tuning
10.6 Resonance suppression
Resonance suppression with manual tuning
When resonance suppression with autotuning cannot reach the suppression effect, you can
proceed as follows to suppress the resonance manually:
1. Activate the current setpoint filters that you want to use (p1656[0].0...3).
2. For the activated current setpoint filters, parameterize the following values:
– Type: general 2nd order filter
– Denominator natural frequency
– Denominator damping
– Numerator natural frequency
– Numerator damping
Note
Assume the notch frequency is f
parameters can be calculated as follows:
• Denominator natural frequency = Numerator natural frequency = f
• Denominator damping = f
• Numerator damping = (f
Parameters
The following list includes the parameters of the "Resonance suppression" function.
Number
p1656[0].0...3
p1657[0]
p1658[0]
p1659[0]
p1660[0]
p1661[0]
p1662[0]
p1663[0]
p1664[0]
p1665[0]
p1666[0]
p1667[0]
p1668[0]
p1669[0]
p1670[0]
p1671[0]
p1672[0]
p1673[0]
p1674[0]
p1675[0]
p1676[0]
310
, notch width is f
sp
/(2 × f
BB
× 10
(k/20)
BB
Name
Activates current setpoint filter
Current setpoint filter 1 type
Current setpoint filter 1 denominator natural frequency
Current setpoint filter 1 denominator damping
Current setpoint filter 1 numerator natural frequency
Current setpoint filter 1 numerator damping
Current setpoint filter 2 type
Current setpoint filter 2 denominator natural frequency
Current setpoint filter 2 denominator damping
Current setpoint filter 2 numerator natural frequency
Current setpoint filter 2 numerator damping
Current setpoint filter 3 type
Current setpoint filter 3 denominator natural frequency
Current setpoint filter 3 denominator damping
Current setpoint filter 3 numerator natural frequency
Current setpoint filter 3 numerator damping
Current setpoint filter 4 type
Current setpoint filter 4 denominator natural frequency
Current setpoint filter 4 denominator damping
Current setpoint filter 4 numerator natural frequency
Current setpoint filter 4 numerator damping
, and notch depth is K, then the filter
BB
)
sp
)/(2 × f
)
sp
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA
sp
Unit
 
 
[Hz]
 
[Hz]
 
 
[Hz]
 
[Hz]
 
 
[Hz]
 
[Hz]
 
 
[Hz]
 
[Hz]
 