Description
Converter variant of 1 AC/3 AC 200 V ... 240 V
For US/Canadian installations (UL/cUL): The products are cULus-listed under File E355661.
• Suitable for use in a circuit that cannot provide more than 100 kA rms (symmetrical), max.
240 V.
Note: The maximum permissible short-circuit current for 200 V variants with Type E
Combination Motor Controllers is 65 kA.
• Protection of the branch circuit for individual drives must be guaranteed using Class J fuses
in accordance with the technical data.
For other protection equipment and SCCRs (Short Circuit Current Rating) for individual
drives, see:
Protective Devices for SINAMICS S200 Product Line
support.industry.siemens.com/cs/ww/en/ps/29596/man)
• This device must be installed in an enclosure that provides an environment with degree of
pollution 2 (controlled).
• Maximum rated temperature 45 °C.
• The device provides overtemperature and overload protection.
• Use copper wires with a permissible temperature of 75 °C for all power cables. You can also
use cables with a higher rated temperature value. It is not permissible to reduce the
conductor cross-section.
Converter variant of 3 AC 380 V ... 480 V
For US/Canadian installations (UL/cUL): The products are cULus-listed under File E355661.
• Suitable for use in a circuit that cannot provide more than 65 kA rms (symmetrical), max.
480 V.
• Protection of the branch circuit for individual drives must be guaranteed using Class J fuses
in accordance with the technical data.
• For other protection equipment and SCCRs (Short Circuit Current Rating) for individual
drives, see:
Protective Devices for SINAMICS S200 Product Line
support.industry.siemens.com/cs/ww/en/ps/29596/man)
• This device must be installed in an enclosure that provides an environment with degree of
pollution 2 (controlled).
• Maximum rated temperature 45 °C. Maximum height 4000 m.
SINAMICS S200 pulse train servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646767B AA
(https://