10.4 Gain switching
10.4

Gain switching

Overview
The function of gain switching is used to switch between two sets of scaling factors.
With the gain switching function, you can implement the following operations:
• Increase the gains during servo lock and decrease gains to reduce noise during rotation.
• Increase the gains during settling to shorten the stop settling time.
• Ensure the stability of the servo system when the load inertia moment ratio varies greatly
during a stop.
Note
Set the scaling factors according to the following formulas to obtain expected servo gains:
• Position loop gain = p29178*p29110 (fast PTI mode)
• Speed loop gain = p1460*p29120
• Speed loop integral time = p1462/p29121
Requirement
• Do not use the function in the torque control mode.
• Disable the functions of autotuning.
Description of function
The function of gain switching is disabled by default (p29130 = 0), and only scaling factor 1 is