2. Verify that the Ethernet Link LED, which is the green LED on the left, is on. If
the LED is on, go to step 3. If it is not on, go to "Final Diagnostic Tests" on
page 208 and return it with your unit. Exit this MAP.
3. Verify that the yellow Speed LED, which is the yellow LED on the right,
correctly reflects the speed of the network. To determine the speed of the
network, Go to "Perform Health Check" on page 159.
4. If the Health Check generates a Trap Event Code of 115, then the ADIC
Gateway yellow Speed LED should be on. If it is, go to Step 6. If it is not, go to
Step 5.
5. Inform the System Administrator that there may be a problem with the
Ethernet cable quality, the intermediate link speeds or interconnect speeds. If
no problems can be found and ADIC Gateway yellow Speed LED does not
come on, go to "Final Diagnostic Tests" on page 208 and return it with your
unit. Exit this MAP.
6. Remove the Ethernet cable from the ADIC Gateway Ethernet Port and attach
the Ethernet loop back plug provided in the Service Tool Kit.
7. Verify that the Ethernet LEDs are functioning correctly. If they are not, inform
the system administrator that there is a network hardware problem where the
ADIC Gateway is attached.
8. Remove the Ethernet loop back plug. Obtain another Ethernet cable. Use this
cable to attach the ADIC Gateway to the local area network.
9. Connect the service terminal to the Service Port (see "Connecting to the
Service Port" on page 217").
10. Press the Enter key on the service terminal. If the prompt is not displayed, go
to "Service Port MAP" on page 191 to determine whether the RS-232 cable
and service terminal are working properly.
188
Ethernet MAP