/ Vpn / Wan" Group - WAGO I/O System 750 Manual [Page 229]">
Download Table of Contents Contents Print this page

Table 133: Wbm "Interface Configuration" Page - "Firewall Configuration Bridge <N> / Vpn / Wan" Group - WAGO I/O System 750 Manual

Hide thumbs Also See for I/O System 750:
Table of Contents

Advertisement

WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
Table 133: WBM "Interface Configuration" Page – "Firewall Configuration Bridge <n> / VPN / WAN"
Group
Parameter
Firewall enabled for
Interface
ICMP echo protection
ICMP echo limit per second
ICMP burst limit
(0 = disabled)
Service enabled
Click the [Submit] button to apply the change. The change takes effect
immediately.
Explanation
Enable or disable the firewall for the respective
bridge.
Enable or disable the "ICMP echo" protection for the
respective bridge.
If you enable ICMP echo protection, all ICMP echo
requests (pings) will be rejected and the ICMP echo
limit per second and ICMP burst limit entries will be
ineffective.
You can specify the maximum number of "ICMP
pings" per second.
Input is only effective when ICMP echo protection is
disabled.
"0" = "Disabled"
You can specify the maximum number of "ICMP
echo bursts" per second.
Input is only effective when ICMP echo protection is
disabled.
"0" = "Disabled"
FTP/FTPES
FTPS (implicit)
HTTP
HTTPS
I/O-CHECK
PLC Runtime
PLC WebVisu –
direct link (port 8080)
SSH
BootP/DHCP
DNS
SNMP
OPC UA (Port 4840)
BACnet (Port 47808)
PROFINET IO
DNP3 (port 20000)
IEC60870-5-104 (port 2404)
IEC61850 (port 102)
Version 1.7.0, valid from FW Version 04.01.10(23)
Appendix 229
Enable or disable the
firewall for the
respective service.
The services
themselves must be
enabled or disabled
separately on the
"Ports and Services"
page.
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-8210/040-000

Table of Contents