220 Appendix

15.2.1.3.2 "BACnet Configuration" Page

You can make special settings for the BACnet fieldbus on this page.
Click the [Submit] button to apply a setting.
Changes made to the BACnet configuration are not applied until after a restart.
Use the WBM Reboot function to restart the stack/controller. Click the [Restart]
button to restart the runtime. Do not shut down the controller too early!
"BACnet Service" Group
You can enable/disable the fieldbus in this group.
The "Service active" parameter must be enabled (default setting) for the BACnet
fieldbus protocol to be used.
On a runtime restart a security message is displayed in a pop-up window asking
if you really want to perform a restart.
Table 123: WBM Page "BACnet Configuration" – "BACnet Settings" Group
Parameter
Service active
Runtime restart
[Restart]
"BACnet Settings" Group
The basic settings for the fieldbus are given in this group.
Table 124: WBM Page "BACnet Configuration" – "BACnet Settings" Group
Parameter
Port number
Who-Is online interval time
(sec)
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
750-8210/040-000 PFC200; G2; 4ETH; XTR
Meaning
Enable/disable the BACnet fieldbus.
Use this button to restart the runtime.
Meaning
Set the port for BACnet fieldbus communication.
Here, you can specify the intervals at which the
controller transmits queries to the fieldbus about
which other subscribers are online (minimum: 60
seconds).