Power Supply; Table 15: Technical Data - Power Supply - WAGO I/O System 750 Manual

Hide thumbs Also See for I/O System 750:
Table of Contents

Advertisement

42
Properties
4.3.3

Power Supply

Table 15: Technical Data – Power Supply
System supply voltage
Input current
(24 V system)
Power failure time acc. IEC 61131-2
Internal system voltage
Power supply efficiency
load
Internal power consumption
(5 V system)
Total current for I/O modules
(5 V system)
Supply voltage (field)
Number of outgoing power jumper
contacts
Current carrying capacity of power
jumper contacts
Derating (supply voltage)
For surrounding air temperature
For surrounding air temperature
For surrounding air temperature
Isolation
Dielectric strength of insulation
1)
Including residual ripple of 15 %
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
at nominal load
typ.
at nominal
typ.
+15 ... +35 °C 17.4 ... 31.2 V (24 V −27.5 ... +30 %)
−40 ... +55 °C 17.4 ... 28.8 V (24 V −27.5 ... +20 %)
+55 ... +70 °C 17.4 ... 26.4 V (24 V −27.5 ... +10 %)
WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
24 VDC (SELV/PELV)
• Power supply via pluggable connector
(CAGE CLAMP
• Derating must be observed!
500 mA
Depending on external buffering
5 VDC (generated via integrated power
supply)
90 %
510 mA
1700 mA
24 VDC (SELV/PELV)
• Power supply via pluggable connector
(CAGE CLAMP® connection)
• Transmission via power jumper
contacts
• Derating must be observed!
2
10 A
1 kV (DC 1 min.,
between system and field level)
1 kV impulse voltage
(Class VW1 per EN 60870-2-1)
®
connection)
1)
1)
1)

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-8210/040-000