Temporarily Setting Fixed Ip Addresses - WAGO I/O System 750 Manual

Hide thumbs Also See for I/O System 750:
Table of Contents

Advertisement

WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
</dg_
8.3.4

Temporarily Setting Fixed IP Addresses

This process temporarily sets the IP addresses for the network interfaces
X1 ... X<n> to fixed IP addresses.
For each bridge used, the assigned interfaces are assigned their own address,
whereby bridge 1 receives the IP address "192.168.1.17", bridge 2 the IP
address "192.168.2.17" and so on.
No reset is performed.
To set temporary fixed IP addresses, proceed as follows:
1.
Set the mode selector switch to STOP and
2.
Press and hold the Reset button (RST) for longer than 8 seconds.
Execution of the setting is signaled by the "SYS" LED flashing orange.
If you make changes to the IP configuration of a bridge after activating the
temporary IP addresses, the new settings are permanently adopted and applied
immediately. The configured bridge exits the temporary IP address mode. The
other bridges keep the temporarily set IP address until restart / reset.
To cancel this setting, proceed as follows:
Perform a software reset or
Switch off the controller and then switch it back on.
Version 1.7.0, valid from FW Version 04.01.10(23)
Commissioning 113
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-8210/040-000

Table of Contents