Table 66: Error Code 9, Explanation of Blink Codes and Procedures for Troubleshooting
Error
Argument
1
2
3
4
5
Cause
Invalid program
statement
Stack overflow
Stack underflow
Invalid event (NMI)
Local bus watchdog
has triggered.
Version 1.7.0, valid from FW Version 04.01.10(23)
Remedy
Malfunction of the program sequence:
-
Contact WAGO Support.
Malfunction of the program sequence:
-
Contact WAGO Support.
Malfunction of the program sequence:
-
Contact WAGO Support.
Malfunction of the program sequence:
-
Contact WAGO Support.
For CODESYS V3 applications:
-
Check the system load by IEC tasks
with priorities 1 ... 14 in the runtime
system (see Section "CODESYS V3"
Runtime Environment >
"CODESYS V3 Priorities").
For C applications:
-
Check the time monitoring settings.
Diagnostics 155