Parameter Table 133 (DI 1)
Register Name, Type
0
1
2
Parameter Table 134 (DI 2)
Register Name, Type
0
1
32
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Bits, Explanation
DI1_FILT,
0 ... 15
UINT
Filter time
DI1_INVERT,
0 ... 15
UINT
Logic
DI1_FUNC,
0 ... 15
UINT
DI 1 function
Bits, Explanation
DI2_FILT,
0 ... 15
UINT
DI2_INVERT,
 ... 15
UINT
Logic
Table 4: Parameter Table 133 (DI 1)
Value/Range
Description
(Default)
0 ... 65535
The filter is used to suppress spurious
(Default: 10)
pulses. Input signals whose pulse length is
less than the filter time are not evaluated.
Specified as n × 100 µs
0 (default)
DI 1 not inverted.
1
DI 1 inverted.
0 (default)
Digital input
The status of DI1 is only shown in the
process image, not evaluated internally.
The value is inverted according to regis-
ter 1.
1
Limit switch, valve 1
The status of DI1 is shown in the process
image and is evaluated internally if the ac-
tuator approaches a limit switch that is con-
nected to input DI1. The status of DI1 is in-
verted according to register 1.
2
STOP, valve 1
The current setpoint "0" is approached with
a stop ramp as long as the stop button is
held down.
Note:
The present target current is approached
with the ramp selected by RSEL as soon as
the button is released.
3
HOLD, valve 1
Hold current setpoint.
4
JOG+, valve 1
OR-operator with JOG_POS bit from
V1_CTRL
5
JOG−, valve 1
OR-operator with JOG_POS bit from
V1_CTRL
6
JOG+, valve 2
OR-operator with JOG_POS bit from
V2_CTRL
7
JOG−, valve 2
OR-operator with JOG_POS bit from
V2_CTRL
Table 5: Parameter Table 134 (DI 2)
Value/Range
Description
(Default)
0 ... 65535
Filter time.
(Default: 10)
The filter is used to suppress spurious
pulses. Input signals whose pulse length is
less than the filter time are not evaluated.
Specified as n × 100 µs
0 (default)
DI 2 not inverted.
1
DI 2 inverted.