Operation Problems - KEB COMBIVERT F5 Reference Manual

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Diagnostics and Troubleshooting

7.3 Operation Problems

Troubleshooting Operation Problems and potential solutions. Refer to Section 7.4 for additional Diag-
nostics Solutions. Additional troubleshooting of learn procedures are listed as well at the end of this
section.
Problem
Motor Does Not Move
294
Cause/Solution/Troubleshoot
Check the Motor Current. Refer to Motor Draws High Current for
additional troubleshooting.
Make sure the brake is picking and/or not dragging.
Make sure speed is set correctly in LS02.
Check the Inverter Status to determine whether there is indication a run
command is being given (i.e. Up/Down Constant Speed/Acceleration/
Deceleration, etc.).
Check Input Status to determine whether the correct inputs are being
signaled for a run command.
Check the Command Speed to determine what the dictated speed
command is.
Check the Active Speed and Active Profile to determine what speed
setting is being selected.
For digital inputs, check setting of the selected Active Speed or
Active Profile.
For analog speed commands, check the Raw and Processed
(Analog) Patterns, the High Speed setting, and speed settings for
any Active Profile.
Check to make sure the speed control gains (KP, KI Offset) are not
set too low.
For open loop induction motors, the Low Speed Torque Boost may
need to be increased to lift the load or decreased if either the Maximum
Torque of Inverter Peak Current limit is reached.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents