KEB COMBIVERT F5 Reference Manual page 275

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Error/Message Alt. /
(NUM)
Error
EInI
Initialization
(57)
MFC
Error Low
Ebr
Motor Current
(56)
*Additional information at end of section
Diagnostics and Troubleshooting
Description
Cause/Solution/Troubleshoot
Control card
Replace control card.
processor unable
to boot.
Error current
Possible causes for low motor current error during
check.
current check:
Prior to every run
the drive sends
current to each
phase of the
motor to verify
the connection.
Afterward, the
drive applies
magnetizing
current (Induction
Motors) and
monitors whether
the motor is
magnetized or
not.
The phase current check can be bypassed by setting
LX08 = Magnetizing Current Check (Induction Motors
only).
If the error occurs when trying to run on open loop,
increase LC32 Low Speed Torque Boost; suggested
value is 5%.
Motor contactor contacts are burnt or damaged.
Bypass motor contactor (do not simply jumper!) to
test and replace as needed.
One or more motor leads is not connected.
Motor contactor is not closing or not closing in time
Bypass motor contactor or verify switching time.
Motor windings are damaged.
Measure motor resistance.
275