FB - Field Bus Parameters
Control Word (16-bit)
The control word consists of serial inputs.
The raw inputs may be masked with parameter FB05 Control Word Mask.
Bit:
Function:
0
Enable
1
Reset
2
Up
3
Down
4
Binary Speed Input 1
5
Binary Speed Input 2
6
Binary Speed Input 3
7
Reserved
8
Reserved
9
Special Function 1
10
Special Function 2
11
Special Function 3
12
Special Function 4
13
Special Function 5
14
Special Function 6
15
Special Function 7
Bits 0 - 3
Basic control word bits consisting of Enable, Up, Down, and Reset.
Bits 4 - 8
Assignment of serial selected binary-coded inputs for either speed or position.
Bits 9 - 15
Serial input selection of special functions. Serial and discrete digital inputs
are independent unless assigned the same function; therefore, it is possible
to have up to 14 functions defined between both serial and digital inputs.
Serial and/or digital inputs assigned the same function will be OR activated.
The available functions are the same as those for discrete digital inputs,
described further under LI04.
or Binary Position 1
or Binary Position 2
or Binary Position 3
or Binary Position 4
or Binary Position 5
237