LM08
Electric Motor
Protection
LM - Motor Data Parameters
This parameter is used to activate and select the type of motor overload
function. Depending on the setting of this parameter, the Elevator Drive will
trigger an 'Error Motor Protection' fault causing the motor to stop.
Settings:
Off
On
Default = On (1)
The trigger level is established in parameter LM09 Electric Motor Protection
Current.
The trip curve is in accordance with VDE 0660 Part 104, UL508C section 42,
and NFPA 70 Article 430 part C. It is defined as follows:
100% of trip current => continuous running
120% of trip current => trip after 2 hours
150% of trip current => trip after 2 minutes
200% of trip current => trip after 1 minute
800% of trip current => trip after 5 seconds
Time
Fan cooled motor
f = 0 Hz
120 min
60 min
30 min
2 min
1 min
30 sec
5 sec
50
100
This function must be activated to ensure the motor protection function
is operational!
The trigger level is established from the LM03 Motor Rated Current and LM11
Peak Motor Current Factor. Refer to LM11 Peak Motor Current Factor for
additional details.
NUM
0
1
Non-ventilated motor
150
200
400
% of Motor
Current
600
800
147