LI - Input Parameters
LI60
Correction / Inspection
140
When this function is turned on, it allows the controller to command the
drive to switch between correction and inspection speeds. This parameter
only applies to Binary Speed Control (1).
LI60 OFF
1. If you start in correction speed and drop the enable while still running a
Drive Enable Switched off is logged.
2. If you start in High speed and drop the enable while still running a
Drive Enable Switched off is logged.
This is expected behavior for both situations.
LI60 ON
1. If you start in correction speed and transition to either inspection or
stay in correction and drop the enable while running no Drive Enable
Switched off is logged.
2. If you start in High speed and drop the enable while still running a
Drive Enable Switched off is logged.