Technical Data
Inverter Size
Max Motor Power
Housing Size
Unit Hardware
Input Ratings
Supply voltage frequency [Hz]
UL minimum wire gauge
UL maximum wire gauge
Output Ratings
Rated output power [kVA]
Rated output current [A]
Peak current (30 seconds)
Over current fault (E.OC) trip level [A]
Rated switching frequency [kHz]
Maximum switching frequency
Power loss at rated operation
Stall current at 4kHz [A]
Stall current at 8kHz [A]
Stall current at 16kHz [A]
Braking Circuit
Min. braking resistance [Ohm]
Typ. braking resistance [Ohm]
Max. braking current [A]
Installation Information
Max. shielded motor cable length
Tightening torque for power terminals [in lb]
Environmental
Max. heat sink temperature TOH [°C]
Storage temperature [°C]
Operating temperature [°C]
Housing design / protection
Approvals
Tested in accordance with...
Standards for emitted interference
Standards for noise immunity
1) The wire gauge is based on the maximum fuse rating, copper wire with a 75°C insulation rating, THHW or equivalent. If circuit protection is selected
based on the actual input current, the wire size could be reduced.
2) This is the peak output current limited by hardware regulation. The software current control reserves 5% for closed loop regulation.
3) This is the maximum carrier frequency the power stage can support. The actual operating carrier frequency is adjusted and limited by the control
card.
4) This is the power dissipation at the rated carrier frequency, rated voltage, and rated load. Operation at reduced carrier frequencies or reduced load
will decrease this value.
5) Max motor cable length when using shielded cable, KEB EMI filter, and the installation must conform to EN55011 / EN55022.
28
[hp]
Supply voltage [V]
Input phases
Rated input current [A]
1)
[awg]
1
[awg]
Rated motor power [kW]
2)
[A]
Output voltage [V]
Output frequency [Hz]
3)
[kHz]
4)
[W]
5)
[ft]
Relative humidity
Climatic category
19
20
21
40
50
60
R
R
B
B
180...260 +/- 0 (240V Nominal Voltage)
50 / 60 +/- 2
3
3
126
143
169
2
2
4/0
4/0
1/0
46
59
71
30
37
45
115
130
154
230
217
270
276
270
315
3 x 0...V input (3 x 0...255V
Generally 0 to 599Hz (limited by control board and carrier frequency)
8
8
16
16
16
1200
1400
1700
123
160
198
115
145
180
70
101
101
3.9
2.0
2.0
4.7
3.9
3.0
102
160
160
165
53
90°C / 194°F
-25...70 °C / -13...158°F
-10...45 °C / 14...113°F
Chassis / IP20 / Pollution Degree 2
max. 95% without condensation
EN 61800-3 /UL508C
EN 55011 Class B / EN 55022 Class A
IEC 1000-4-2 / -3 / -4 / -5/ -6
3K3 in accordance with EN 50178
23
100
R
U
B
B
D
3
3
264
6
2
300 kcmil
115
75
224
363
450
435
540
2)
)
8
4
8
3000
319
396
203
252
1.2
1.2
1.5
1.5
340
340
220