KEB COMBIVERT F5 Reference Manual page 207

Elevator drive
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

LP05
Correction Distance
LP - Positioning Parameters
The corrective distance can be used to reset the position error as the car comes
to the floor. When the drive sees the leveling zone marker, the position counter
is reset to reflect the actual distance entered in this parameter. The controller
passes the leveling zone sensor signal to the drive via an input programmed
as 'Position Deviation Reset' . Refer to input parameters LI04-11 for further
information on programmable input functions.
With this parameter the amount of stabilized leveling can be adjusted. A value
of zero means no correction, the function is off and the leveling distance is the
distance adjusted in the controller.
A value of 6.0" , the distance of the leveling zone to the dead zone, will provide
no leveling and the system will be on the verge of over shooting the floor.
The optimum adjustment for direction to the floor operation is a value of
5.7" . ..5.9" . If a little leveling is desired set the value to 5.0" . ..5.5" .
LS01
LP05 = 5.8 inches
207